PEPPERL + FUCHS ISOLATED AMPLIFIER KCD2-SR-EX1.LB Specification

  • Cooling Method
  • Natural air cooling
  • Operating Temperature
  • -20 C to +60 C
  • Output Current
  • 250 mA max (relay contact)
  • Connector Type
  • Screw terminals
  • Features
  • 1-channel, relay output, mounting on DIN rail, galvanic isolation, Ex-approval for hazardous area
  • Application
  • Intrinsically safe signal transmission for sensors and switches in hazardous areas
  • Power Supply
  • Terminal connection
  • Output Type
  • Relay (SPDT), contact
  • Working Temperature
  • -20 C to +60 C
  • Product Type
  • Isolated Amplifier
  • Input Voltage
  • 19 V DC to 30 V DC
  • Voltage Protection
  • Overload and short-circuit protected
  • Material
  • Plastic (housing)
  • Storage Temperature
  • -40 C to +85 C
  • Weight
  • Approx. 150 g
  • Response Time
  • <10 ms
  • LED Indication
  • Power / status LED
  • Mounting Type
  • DIN Rail
  • Signal Type
  • Namur sensor or contact
  • Hazardous Area Compatibility
  • Zone 0, Zone 1, Zone 2
  • Dimensions
  • 12.5 mm x 115 mm x 126 mm (W x H x D)
  • Series
  • K-System
  • Relay Contact Rating
  • 250 V AC / 2 A
  • Model Number
  • KCD2-SR-EX1.LB
  • Protection Category
  • IP20
  • Switching Capacity
  • 500 VA / 60 W
  • Channel
  • 1-channel
  • Switching Voltage
  • 250 V AC / 24 V DC
  • Relay Configuration
  • SPDT
 
 

About PEPPERL + FUCHS ISOLATED AMPLIFIER KCD2-SR-EX1.LB



Order today to experience the matchless performance of the PEPPERL + FUCHS ISOLATED AMPLIFIER KCD2-SR-EX1.LB, a premier choice for intrinsically safe signal transmission in hazardous environments. Featuring favorable reviews from industry professionals, this classic device supports Namur sensors or contacts, and boasts a robust SPDT relay output for maximum versatility. Its special design includes fast response time (<10 ms), LED indication, overload protection, and Ex-approval for Zones 0, 1, and 2. Secure mounting on DIN rails and high reliability make it the lead solution for safety-critical applications.

Key Features and Application Advantages

The KCD2-SR-EX1.LB stands out with galvanic isolation, efficient relay output, and natural air cooling for enhanced reliability. Its compact, durable design fits into tight control panels with ease. Specifically engineered for use in hazardous areas, it supports a wide voltage range and offers LED status indication. Competitive advantages include Ex-approval compliance and robust overload protection. Ideal for premier industrial environments, it excels in transmitting signals from field sensors and switches safely and efficiently.


Domestic Market Presence, Supply, and Delivery Policy

Supplying across India, the KCD2-SR-EX1.LB is readily available with a reliable drop-off and delivery system. Our supply ability meets both large and small orders, ensuring seamless fulfillment. Quotation requests are processed promptly to support efficient procurement cycles. To help customers assess product compatibility, a flexible sample policy is available upon request. Experience streamlined service and professional support from inquiry to installation.


FAQs of PEPPERL + FUCHS ISOLATED AMPLIFIER KCD2-SR-EX1.LB:


Q: How does the KCD2-SR-EX1.LB ensure safety in hazardous areas?

A: The KCD2-SR-EX1.LB is Ex-approved for use in Zones 0, 1, and 2, featuring galvanic isolation and robust voltage protection, ensuring intrinsically safe signal transmission even in highly hazardous environments.

Q: What primary features set this isolated amplifier apart from competitors?

A: Its matchless features include a fast response time, SPDT relay output, LED indication for power/status, wide input voltage range, overload protection, and straightforward DIN rail mounting. These make it a premier solution for demanding settings.

Q: When should the KCD2-SR-EX1.LB be used in industrial applications?

A: It should be used for classic intrinsically safe signal transmission from Namur sensors or contacts in hazardous or explosive atmospheres, where reliable protection and quick response are required.

Q: Where is the KCD2-SR-EX1.LB typically installed?

A: Designed for DIN rail installation, this amplifier is ideally suited for control panels and enclosures in process industries, oil and gas facilities, and other safety-critical environments across India.

Q: What is the process for obtaining a quote and sample for the KCD2-SR-EX1.LB?

A: You can request a quotation by contacting our sales team. For product evaluation, we offer a sample policy; simply specify your requirement, and we will arrange delivery through our reliable drop-off system.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in PEPPERL + FUCHS Used Materials Category

PEPPEL  FUCHS BARRIER

PEPPEL FUCHS BARRIER

Working Temperature : 20C to +60C

Output Type : Other, Analog/Digital signal barrier

Storage Temperature : 25C to +70C

Application : Intrinsic Safety, Hazardous areas, Process Automation

Product Type : Explosion Protection Barrier

Cooling Method : Natural Air Cooling

AMPHENOL P28820

AMPHENOL P28820

Working Temperature : 40 to +85

Output Type : Single

Storage Temperature : 55 to +125

Application : Industrial Electronics, Automation, Communication

Product Type : DCDC Converter Module

Cooling Method : Natural Air Convection

Single Phase PEPPERL+FUCHS KFD2-CRG-EX1D

Single Phase PEPPERL+FUCHS KFD2-CRG-EX1D

Working Temperature : 20C to +60C

Output Type : Other, Relay Contact (SPDT)

Storage Temperature : 25C to +70C

Application : Safe switch for hazardous area signals, automation systems

Product Type : Single Phase Isolated Barrier Relay Module

Cooling Method : Natural convection

PEPPEL  FUCHS BARRIER

PEPPEL FUCHS BARRIER

Working Temperature : 20C to +60C

Output Type : Other, Isolated Signal Output

Storage Temperature : 25C to +70C

Application : Hazardous Area Signal Isolation

Product Type : Intrinsically Safe Barrier

Cooling Method : Natural Air Cooling